Pre-action systems, sensitive equipment protection
The main risk of water extinguishing in a data center is not just the fire itself but also accidental water flow: the activation of a sprinkler due to mechanical damage can render operational equipment inoperable. Therefore, server and UPS rooms are usually kept dry (empty) in the network.
In a pre-action system, the pipes are filled with compressed air, and water is only released when TWO conditions are met simultaneously: the detector confirms the fire, and the sprinkler opens due to heat. Thus, mechanical damage (for example, a strike to the sprinkler) does not cause water flow — the system interprets this as a loss of air pressure and alerts.